The simple equation which we use for calculating sensible load is
Qs=1.08∗CFM∗ΔT
The above equation is derived from
Qs=m∗Cp∗ΔT
Where, Qs - Sensible load
m - Mass flow rate of air Cp - Specific heat of air ΔT - Temperature difference
To get the sensible load in Btu/hr by entering the air flow rate in cfm (cubic feet per minute), the other variables should have the below specified units.
mass flow rate in lb/ft3-hr,
Specific heat in Btu/lb-°F,
Temperature difference in °F
Mass flow rate of air = mass/volume
Density of air = 0.075 lb/ft3 at atmospheric pressure and 70oF
1 cfm = 60 ft3/hour
Specific heat of air = 0.24 Btu/lb−oF
Substitute the above values and we get
Qs=(0.075∗cfm∗60)∗0.24∗ΔT=1.08∗cfm∗ΔT
Latent cooling/heat load
The simple equation which we use for calculating latent load is
Ql=0.69∗CFM∗ΔW
The above equation is derived from
Ql=m∗L∗ΔW
Where, Ql - Latent load
m - Mass flow rate of air
L - Latent heat of water ΔW - Difference in humidity ratio
To get the sensible load in Btu/hr by entering the air flow rate in cfm (cubic feet per minute), the other variables should have the below specified units.
mass flow rate in lb/ft3-hr,
Latent heat of water in Btu/lb
Latent heat of water vapour = 1094 Btu/lb at atmospheric pressure and 75oF
Latent heat of condensed water = 18 Btu/lb at atmospheric pressure and 75oF
Latent heat of vapourizing water = 1094-18 = 1076 Btu/lb at atmospheric pressure and 75oF
Density of air = 0.075 lb/ft3 at atmospheric pressure and 70oF
1 cfm = 60 ft3/hour
Specific heat of air = 0.24 Btu/lb−oF
Substitute the above values and we get
Ql=(0.075∗cfm∗60)∗1076∗ΔW=4842∗cfm∗ΔW
Where,
ΔW is in lb/lb
Ql=4842∗cfm∗ΔW/7000=0.69∗cfm∗ΔW
Where,
ΔW is in gr/lb
ΔW can be calculated from Humidity ratio, when you have DBT & WBT at inlet/outlet.
Total cooling/heat load
Total load can be calculated by adding above two values viz., sensible load and latent load.
Qt=Ql+Qs
OR we can calculate using below equation
Qt=m∗ΔH
Where, Qt - Total load
m - Mass flow rate of air ΔH - Difference in Specific Enthalpy
Qt=0.075∗cfm∗60∗ΔH=4.5∗cfm∗ΔH
Where, Qt - Total load in Btu/hr ΔH - Difference in Specific Enthalpy in Btu/lb
Sensible Heat Factor (SHF)
Sensible heat factor can be calculated using below equation