AHU air side cooling load calculation
Sensible cooling/heat load
The simple equation which we use for calculating sensible load is
The above equation is derived from
Where, - Sensible load m - Mass flow rate of air - Specific heat of air - Temperature difference
To get the sensible load in Btu/hr by entering the air flow rate in cfm (cubic feet per minute), the other variables should have the below specified units.
mass flow rate in lb/ft3-hr, Specific heat in Btu/lb-°F, Temperature difference in °F
- Mass flow rate of air = mass/volume
- Density of air = 0.075 at atmospheric pressure and
- 1 cfm = 60
- Specific heat of air = 0.24
Substitute the above values and we get
Latent cooling/heat load
The simple equation which we use for calculating latent load is
The above equation is derived from
Where, - Latent load m - Mass flow rate of air L - Latent heat of water - Difference in humidity ratio
To get the sensible load in Btu/hr by entering the air flow rate in cfm (cubic feet per minute), the other variables should have the below specified units.
mass flow rate in lb/ft3-hr, Latent heat of water in Btu/lb
- Latent heat of water vapour = 1094 Btu/lb at atmospheric pressure and
- Latent heat of condensed water = 18 Btu/lb at atmospheric pressure and
- Latent heat of vapourizing water = 1094-18 = 1076 Btu/lb at atmospheric pressure and
- Density of air = 0.075 at atmospheric pressure and
- 1 cfm = 60
- Specific heat of air = 0.24
Substitute the above values and we get
Where,
is in lb/lb
Where,
is in gr/lb
can be calculated from Humidity ratio, when you have DBT & WBT at inlet/outlet.
Total cooling/heat load
Total load can be calculated by adding above two values viz., sensible load and latent load.
OR we can calculate using below equation
Where, - Total load m - Mass flow rate of air - Difference in Specific Enthalpy
Where, - Total load in Btu/hr - Difference in Specific Enthalpy in Btu/lb
Sensible Heat Factor (SHF)
Sensible heat factor can be calculated using below equation